Thông số kỹ thuật
| Current rating |
16A and 32A |
| Voltage rating |
115V or 230V, ±15% |
| Type |
1-Phase/2-Pole |
| Frequency |
50Hz and 60Hz, ±10% – Auto detection |
| Transfer type |
Break-Before-Make zero current transfer by Thyristors / SCR |
| Synchronous break time |
10ms typical |
| MTBF |
>1,000,000 hours |
| Maintenance bypass |
None |
| Isolation |
Optional incoming source isolator switches, front mounted |
| Display |
Bi-colour LED mimic decal with load indication |
| Interface |
Preferred supply selection, Source transfer selection and Alarm cancel button |
| Contact |
One voltage free general alarm indicator, Form A or Form B – SPST |
| Ethernet |
LAN optional |
| Input options |
16A: IEC C20 sockets
32A: 6mm2 terminals with glands |
| Output options |
16A: 2 x IEC C19 + 8 x IEC C13 sockets
32A: 2 x IEC C19 + 8 x IEC C13 sockets or 6mm2 terminals with glands |
| Dimensions H x W x D |
16A: 1RU/19″ – 44 x 483 x 285mm
32A: 1RU/19″ – 44 x 483 x 307mm |
| Weight |
5 kg |
| Temperature |
0 – 40°C |
| IP rating |
IP31 |
| Detection |
Digital: <1ms |
| Asynchronous break time |
0ms, 10ms, 50ms or Vt proportional, 0° to 180° |
| Loading |
0 -100% @40°C ambient |
| Device ratings |
80Arms, 1400V, 1kA for 1 cycle |
| Overload @40°C ambient |
40A for 30s 115A for 0.1s
63A for 1s 1kA for 1 cycle |
| Fault current setting |
300% peak with load fault transfer inhibit |
| Safe install environment |
20kA, 100A internally fused |
| Protection |
100A fuses – BS88/FE100 |
| Power factor |
No practical limit |
| Max THDV |
10% – Max allowable source voltage distortion |
| Crestfactor |
3 : 1 |
| dV/dt max |
800V/^s |
| Cooling |
Passive |
| Humidity @40°C ambient |
5 – 95% non-condensing |
| Regulatory approvals |
IEC 62310-1,2,3 -IEC 60950 -IEC 61000-6-1,2,3,4 – CE – RCM – UL Capable – RoHS |
| Standard warranty |
24 months offsite repair or replacement policy |